Back to chapter

8.11:

Reducing Line Loss

JoVE Core
Electrical Engineering
A subscription to JoVE is required to view this content.  Sign in or start your free trial.
JoVE Core Electrical Engineering
Reducing Line Loss

Languages

Share

To minimize line losses in three-phase circuits, two transformers are added: a step-up transformer at the source and a step-down transformer at the load. Their inverse turn ratios ensure consistent load voltage and current. The left transformer's secondary voltage is tenfold its primary voltage, and the impedance connected to the right transformer's secondary, as seen from the primary, is multiplied by a factor of 100. Now, replacing the circuit with a single-mesh circuit, the mesh current represents the line current. The current entering the left transformer's secondary end equals the negative line current, while at the primary, it is ten times the negative secondary current. Similarly, the current entering the right transformer's primary end equals the line current, while at the secondary end, it is ten times the primary current. The phase voltage at the load is determined, followed by calculating the power delivered by the source and to the load. Estimating the power lost in the line reveals that 99.5 percent of the power supplied by the source reaches the load, with only 0.5 percent lost in the line.

8.11:

Reducing Line Loss

In a three-phase circuit, line loss is an indicator of energy dissipated as heat due to the resistance of transmission lines. To address this, incorporating transformers into the system—a step-up transformer at the source and a step-down transformer at the load—is a strategic solution. Two three-phase transformers are introduced to improve this.

With a step-up transformer at the source, the voltage is increased, thereby reducing the current in the transmission lines since power loss in transmission lines is proportional to the square of the current, this reduction in current leads to a decrease in line losses.

Calculation of Line Current:

The line current is calculated by dividing the impedance-reflected load (considering the transformer's turns ratio) by the secondary voltage of the transformer.

The line current is:

Equation 1

Equation 2

Where n is the transformer's turns ratio and Zload is the actual load impedance on the secondary side

Calculation of Phase Voltage at the Load:

If the primary to secondary turns ratio of the transformer is given as Np:Ns, then the phase voltage at the load can be found by:

Equation 3

where:

Vphase is the phase voltage at the load,

Vprimary is the phase voltage at the primary side of the transformer

In a Y-to-Y (star-to-star) three-phase system with transformers on both sides, the full line-to-line voltage at the load can be found by multiplying the phase voltage by sqrt 3, due to the phase shift between line voltages in a Y configuration:

Equation 4

The real power P delivered by the source in a three-phase system is:

Equation 5

Where:

P is the total real power delivered by the source.

VL is the line-to-line voltage.

IL is the line current.

cos(θ) is the power factor.